Moulded сase сircuit breakers with electronic block FMC6Ei 3P 800A 85kA

Code: FMC6Ei800

Molded сase сircuit breaker with electronic block FMC6Еі are used in a low-voltage distribution and protection against overcurrent,short circuit switchboard equipment as well as single phase-to-earth fault.

 

CAD files
Molded сase сircuit breaker with electronic block FMC6Ei 800А

 

Standards

IEC/EN 60947-2

Rated release current In, A

800

Long delay current range:

0.4-1.0xIn

Long delay current setting:

320-800A with increment by 1A

Long delay time:

12-150s with increment by 1s+OFF

Short circuit protection of low level faults:

650-8000A with increment by 1A+OFF

Short time:

0.06-1s with increment by 0.02s+OFF

Short circuit protection of high level faults:

1300-9600A with increment by 1A+OFF

Pre trip alarm setting multiple:

228-800A with increment by 1A

Rated frequency, f, Hz

50/60

Rated voltage of the insulation Ui, V

800

Rated voltage Un, V

~690

Number of poles

3

Rated operating breaking capacity Ics, kA
(AC 380/415V)

75

Limiting operating breaking capacity Icu, kA
(AC 380/415V)

1000

Commutation wear resistance (electric/mechanical)

500/2 500

Electronic LCD Display

yes

Front bus connection 

yes

Rear-mounted bus connection 

yes

Connecting of additional devices

yes

Altitude above sea level, m

2000

Operating temperature range, °C

-25…+55

Storage temperature range, °C

-25…+70

Warranty period of operation, years

5

Term of operation, years

not less than 15