Switch disconnector FLPS 250A 3P

Code: FLPS2503

Load break switch disconnector FLPS is used in distribution systems to perform manual switching operations for turning on or off AC electrical networks with a voltage up to 690V and a frequency of 50/60 Hz. The spring-operated mechanism ensures fast switching on or off regardless of the switching speed, significantly improving arc extinguishing capability. The parallel contact with a double break point has a self-cleaning function. The transparent top cover allows visual monitoring of the switch status.

Standard

IEC 60947-3

Rated current In, A

250

Rated voltage Un, V

~415/690

Rated frequency f, Hz

50/60

Rated voltage of the insulation Ui, V

800

Impulse withstand voltage Uimp, V

8

Current at AC23A, 415/690

250/125

Rated short-time current 0,3s Icw, kA

15

Commutation wear resistance
(mechanical/electrical)

10000/1500

Maximum power at AC23A, kW

125

Cross-section of connecting conductors, mm²

120

Protective dielectric cover for terminals connection

yes

Protection class ІР20
Pollution degree 3
Operating position vertical with a possible deviation to the left and right by 90°
Installation method busbars, cable tips
Altitude above sea level, m 2000
Operating temperature range, °C -25...+50
Storage temperature range, °C -40...+60
Warranty period of operation, years  5
Term of operation, years not less than 15
Weight, kg

1.33