Magnetic starters are designed for operation at objects of civil construction, objects of administrative and commercial purposes and industrial facilities in long-term, interrupted long-term, repeated short-term, short-term modes of operation in the absence of shocks and strong fluctuations.
| Standard | IEC/EN 60947-4-1 |
| Rated operating voltage of power contacts Un, V | ~230/400/690 |
| Quantity andtype of additional contacts | 4NO+2NC |
| Rated voltage ofcontrol coil Uc, V | ~230 |
| Operating voltage range of control coil | 85-100% Uc |
| Rated voltage of the insulation Ui, V | 1140 |
| Conventional thermal current (АС-1) Ith, А | 125 |
| Rated operating current(АС-3) Ie, А | 100 |
| Rated power of main contacts by АС-3, kW | 30 / 45 / 75 |
| Power of the coil activation at Uc, W | 450/55 |
| Permissible frequency of operations, cycles per hour | 1200 |
| Connecting of additional devices | yes |
| Commutation wear resistance (АС-3), (electric/mechanical) | 1.2/10 |
| Altitude above sea level, m | 2000 |
| Weight net, kg | 2.65 |
| Warranty period of operation, years | 5 |
| Term of operation, years | not less than 15 |
Додано у кошик