Undervoltage release F/UVs for FMP32 230V

Code: F/UVs230

Functions:

Disconnecting the circuit breaker when the voltage drops or rises to the tripping setting.

Standard IEC/EN 60947-2
Rated voltage Un, V 230-240AC
Rated frequency, f, Hz 50
Commutation wear resistance 6 000 - electric
10 000 - mechanical
Starter shutoff voltage, V 35-70%
Rated voltage of the insulation Ui, V 690
Rated pulse current output voltage Uimp, V 6 000
Warranty period of operation, years

5

Term of operation, years

not less than 15